This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
admin:poweroff [2022/02/09 09:32] peppe |
admin:poweroff [2022/04/19 12:11] (current) peppe |
||
---|---|---|---|
Line 1: | Line 1: | ||
===== Διακοπή ρεύματος και επαναφορά ===== | ===== Διακοπή ρεύματος και επαναφορά ===== | ||
- | Altus KVM 10.1.2.10 | + | PRINT BEFORE USE! |
+ | Material may not be available during shutdown process. | ||
+ | |||
+ | Updated 19/ | ||
+ | \\ | ||
+ | * Altus KVM 10.1.2.10 | ||
+ | * Cisco switch port 6: trunk for recovery | ||
+ | * Backup! Transfer to safe media! | ||
==== Διακοπή ρεύματος ==== | ==== Διακοπή ρεύματος ==== | ||
Line 7: | Line 14: | ||
=== Επίπεδο 1 === | === Επίπεδο 1 === | ||
== HP DL145G2 == | == HP DL145G2 == | ||
- | titan (old printserver), | + | - Close control units poweroff |
- | csforum, iLO 10.1.2.30\\ | + | - titan (old printserver), |
- | aeolus, iLO 10.1.2.150\\ | + | |
- | glaucus\\ | + | |
+ | | ||
+ | - unmount / | ||
+ | |||
+ | == Εργαστήρια == | ||
+ | * Shutdown/ | ||
+ | |||
+ | == 3D printers == | ||
+ | * Tevo Tarantula poweroff | ||
+ | * Sun Ultra20 poweroff | ||
+ | * Z-printer poweroff | ||
+ | * Z-printer storage shutdown (Long button press -> shutdown procedure) | ||
| | ||
== HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2.102 == | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2.102 == | ||
- | titan-printserver (new printserver, | + | - titan-printserver (new printserver, |
- | mysql-server\\ | + | |
- | calliope-www (cse www, calliope-vlan74)\\ | + | |
== HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | ||
- | zeus-debian (zeus-vlan74)\\ | + | * zeus-debian (zeus-vlan74)\\ |
== HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
- | engineering www (jupiter) | + | * engineering www (jupiter) |
== Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
- | examservers | + | * examservers |
=== Επίπεδο 2 === | === Επίπεδο 2 === | ||
== Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
- | gaia | + | * gaia |
== HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | ||
- | uranus-debian | + | * uranus-debian |
=== Επίπεδο 3 === | === Επίπεδο 3 === | ||
== EMC VNXe3100, 10.7.4.9 == | == EMC VNXe3100, 10.7.4.9 == | ||
- | poweroff | + | Poweroff |
Shut down the system | Shut down the system | ||
Line 48: | Line 66: | ||
2. Enter the Service password to access the Service System page. | 2. Enter the Service password to access the Service System page. | ||
3. Under Service Actions, select Shut Down System. | 3. Under Service Actions, select Shut Down System. | ||
- | 4. Click Execute service action to shut down the storage processors (SPs). | + | 4. Click Execute service action to shut down the |
+ | storage processors (SPs). | ||
5. In the Service Confirmation dialog box, click OK. | 5. In the Service Confirmation dialog box, click OK. | ||
- | 6. Check the status of the shutdown process by looking at the SP LED indicators: | + | 6. Check the status of the shutdown process by looking at the |
+ | SP LED indicators: | ||
| | ||
- | On VNXe3100 and VNXe3150 systems, the shutdown process is complete | + | On VNXe3100 and VNXe3150 systems, the shutdown process is complete |
- | only the Storage Processor Power LEDs are blinking and all other | + | |
- | Storage Processor LEDs are off. | + | |
| | ||
- | 7. If you are relocating hardware, disconnect cables in the following order: | + | 7. If you are relocating hardware, disconnect cables in the |
+ | following order: | ||
| | ||
- | Disconnect the power cables from disk-processor enclosure (DPE) to power down the SPs. | + | Disconnect the power cables from disk-processor enclosure (DPE) |
+ | | ||
Disconnect the power cable from the DAEs to power them down. | Disconnect the power cable from the DAEs to power them down. | ||
== HP DL145G2 == | == HP DL145G2 == | ||
- | scylla, iLO 10.1.2.45\\ | + | - scylla, iLO 10.1.2.45\\ |
- | rescue, iLO 10.1.2.49 | + | |
== HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
- | gatepc73\\ | + | - gatepc73\\ |
- | gatepc74\\ | + | |
- | gatepc76\\ | + | |
- | clonezilla SE\\ | + | |
- | charybdis\\ | + | |
+ | |||
+ | == ESXi(s) == | ||
+ | * Shutdown 10.7.4.6 | ||
+ | * Shutdown 10.7.4.7 | ||
+ | * Shutdown 10.7.4.125 | ||
+ | * Shutdown 10.1.2.40 | ||
+ | * Shutdown 10.1.2.41 | ||
+ | |||
+ | == Power cables == | ||
+ | - Unplug all machines | ||
+ | - Turn off, unplug 2x online UPSs | ||
+ | - Turn off, unplug 1x rescue UPS (in rack) | ||
+ | - Unplug Cisco switch | ||
+ | - Unplug HP switch | ||
+ | - Unplug mgmt switch | ||
+ | - Unplug ATEN KVM | ||
== personal machines == | == personal machines == | ||
- | poweroff | + | * poweroff |
==== Επαναφορά ρεύματος ==== | ==== Επαναφορά ρεύματος ==== | ||
Poweron | Poweron | ||
=== Επίπεδο 1 === | === Επίπεδο 1 === | ||
+ | |||
+ | == Power on == | ||
+ | - ATEN KVM | ||
+ | - Cisco switch | ||
+ | - HP switch | ||
+ | - mgmt switch | ||
+ | - 2x online UPSs | ||
+ | - 1x rescue UPS | ||
== EMC VNXe3100, 10.7.4.9 == | == EMC VNXe3100, 10.7.4.9 == | ||
- | poweron procedure | + | Power up the system (20+ minutes! Check www!) |
+ | |||
+ | To power up a system that is fully powered down: | ||
+ | 1. Reconnect the power cables to each DAE in the following exact order: | ||
+ | DAE 0 | ||
+ | DAE 1 | ||
+ | DAE 2 | ||
+ | Power up any remaining DAEs in ascending order. | ||
+ | |||
+ | The green Power Status LED powerlines.gif on each DAE turns on. | ||
+ | For more information on the LEDs, see System LED displays. | ||
+ | 2. Reconnect the power cables to each SP in exactly this order: | ||
+ | SP A | ||
+ | SP B | ||
+ | |||
+ | The green Power Status LED on each SP turns on. | ||
== HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
- | gatepc73\\ | + | - gatepc73\\ |
- | gatepc74\\ | + | |
- | gatepc76\\ | + | |
- | clonezilla SE\\ | + | |
== HP DL145G2 == | == HP DL145G2 == | ||
- | titan (old printserver), | + | - titan (old printserver), |
- | csforum, iLO 10.1.2.30\\ | + | |
- | aeolus, iLO 10.1.2.150\\ | + | |
- | glaucus\\ | + | |
- | scylla, iLO 10.1.2.45\\ | + | |
- | rescue, iLO 10.1.2.49 | + | |
- | + | ||
- | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2. == | + | |
- | titan-printserver (new printserver)\\ | + | |
- | mysql-server (NOT!)\\ | + | |
- | + | ||
- | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | + | |
- | engineering www (jupiter)\\ | + | |
- | charybdis (NOT!)\\ | + | |
Line 109: | Line 162: | ||
== HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | ||
- | uranus-debian | + | * uranus-debian |
+ | * check students FS | ||
+ | * check grads FS | ||
+ | * check staff FS | ||
+ | * check quotas | ||
== Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
- | gaia | + | * gaia |
=== Επίπεδο 3 === | === Επίπεδο 3 === | ||
- | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2. == | + | == HP DL380G6 esxi2, 10.7.4.6, iLO 10.1.2.102 == |
- | calliope-www (cse www)\\ | + | |
+ | - titan-printserver (new printserver)\\ | ||
+ | - mysql-server (NOT!)\\ | ||
== HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | == HP DL380G6 esxi3, 10.7.4.7, iLO 10.1.2.103 == | ||
- | zeus-debian\\ | + | * zeus-debian\\ |
+ | == HP DL380G7 esxi4, 10.7.4.125, iLO 10.1.2.104 == | ||
+ | - engineering www (jupiter)\\ | ||
+ | - charybdis (NOT!)\\ | ||
== Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | == Dell R630 #1 (UP), 10.1.2.40, iLO 10.1.2.110 == | ||
- | examservers (NOT!) | + | * examservers (NOT!) |
+ | == scylla mounts == | ||
+ | * mount / | ||
+ | |||
+ | == Εργαστήρια == | ||
+ | * Power up always on clients | ||
+ | | ||
+ | == 3D printers == | ||
+ | * Sun Ultra20 poweron (+klipper, octoprint start) | ||
+ | * Tevo Tarantula poweron | ||
+ | * Z-printer poweron | ||
+ | * Z-printer storage poweron | ||
+ | |||
+ | == Close control units == | ||
+ | * Power on | ||
+ | |||
+ | | ||